Homestead · heat, air, light

Systems

The house heats, and every light switches, with the server off. The boilers keep their own safety controls and every room keeps a switch that works on its own; the server supervises and schedules, and is never the only way to do anything.

STORAGE TANK: THE HUBpressurized, in the hub, the first buildingHOTCOOLelectric elementWOOD BOILERgasification, indoors in the hubleads whenever the tank is hotloaded from the woodshed; its own chimneyprotectionPROPANE BOILERin the hub, sealed combustionsecond: fires below a lower setpointELECTRICthird, lower setpoint stillor the solar surplusSOLAR PVgrid-tied: the pumps, lightsand heat pump; surplus to the tankGREENHOUSE CAPTUREthe peak's fan coil fills its ownwarm store first, then thisinto the cool bottom, when hotterscaldHOT WATERan indirect tank at each building,priority; mixing valve to ASSE 1017outdoor resetFLOORSburied lines to the workshop, thenthrough the tunnel to the houseAIR HANDLERthe water coil when the tank is hot;the heat pump's coil otherwise, and coolingHEAT PUMPcold-climate,outdoorsGREENHOUSE AND HOT TUBglycol, own pump: above freezingfor the figs and the citrusTHE FIRE'S OWN PATHmasonry heater and Rumford:not on the tank; own footingswaterglycolelectricrefrigerant
SheetS1
TitleHeat schematic
ViewNot to scale
Drawn2026-09-27

Scroll the sheet sideways

One tank, every source, in the hub, a building of its own: boilers are noisy, and no propane ever enters the house. In lead order: the outdoor wood boiler, through its protection valve and a plate exchanger with glycol on the buried side; a propane modulating boiler below a lower setpoint; an electric element below a lower one still or on the solar array's surplus; and the greenhouse's daytime surplus, into its own warm store first and the tank's cool bottom only when hotter (energy).

Out of it: hot water first, to a small indirect tank in each building, each with a mixing valve; the floors on outdoor reset, the workshop's slab and, through the tunnel, the house's; the air handlers' water coils; and the greenhouse and hot tub on their own glycol loop. The masonry heater and the fireplace are the fire's own path, not on the tank.

Built in order: the hub first, whole; its lines to the workshop with the workshop; on through the tunnel with the house; a branch for each building after.

The first heat numbers

An estimate by conductance and air leakage from the drawings' sizes and the envelope's R-values, at a design temperature of −25 °F, the state dwelling code's figure for this county, and about 9,000 heating degree days a year. It is not a Manual J and it sizes nothing; it shows where the heat goes and roughly how much wood it takes.

BuildingHeld atDesign load
The house, 5,600 sq ft above grade and the basement70 °F~73,000 Btu/h
The workshop, 60 × 48, doors sealed well55 °F at work~50,000 Btu/h
The greenhouse, night curtains drawn40 °F at night~57,000 Btu/h
The greenhouse, no curtains40 °F at night~89,000 Btu/h
A yearMillion Btu
The house~141
Hot water for six~13
The workshop, 45 °F idle and 55 °F at work~74
The greenhouse, less the sun's day gain (est. 40 %)~42
The hot tub, covered (est.)~12
Total~281

At a gasifier's ~75 % seasonal efficiency (estimated) that is about 16 of oak and maple; 19 of mixed hardwood; 25 of aspen and pine a year. The house is modest for its size because the envelope works; the air that leaks out of it is its largest loss.

Air and humidity

Every room sensed, every room ducted and zoned: a motorized damper on each room's supply and a radiant loop on each room's actuator, both run by that room's temperature and humidity sensor.

WhereServes
Air handler 1the basement's mechanical roomthe basement, the first floor, the wing and the lean-to, by floor registers from below
Air handler 2the warm attic over the main blockthe second floor, by ceiling registers from above

Each has a hot-water coil from the tank and a cold-climate heat pump coil for cooling and the shoulder seasons.

  • Dry winters: a steam humidifier on each air handler, held under the ceiling a vapour-open wall can take at −20 °F. Foggers only where a room wants its own humidity: the root cellar and the greenhouse, never the house's air.
  • Moist summers: the heat pumps and a whole-house ducted dehumidifier, with the floors' heat locked out; the cellar and the tunnel on a dehumidifier of their own, because a cool cellar is never ventilated with July air.
  • Always: an energy-recovery ventilator for fresh air, bath fans on humidity switches, a ducted kitchen hood with make-up air. In fan-only mode the return near the masonry heater carries its stored warmth through the first floor.
  • The green frame dries in the house. Cut and raised green, the frame gives up roughly 15–17 tons of water over its first few heating seasons (an estimate from green and oven-dry densities); the dehumidifiers and the ventilator carry it out, and the plaster and floors wait for the first heating season.
  • Alarms stay separate: smoke and carbon-monoxide alarms are listed, hardwired and interconnected as code requires, and depend on nothing else.

Light

  • Incandescent where people live, by the legal routes left since the 45 lm/W rule ended the sale of general-service incandescent lamps in 2023: multi-lamp fixtures of 25 W lamps (under 310 lumens a lamp is not a general-service lamp), 100 W G40 globes, and plug-in table and floor lamps on switched receptacles.
  • LEDs where nobody lives: the basement, the mechanical and server rooms, closets, the pantry and laundry, the porches, the garage and workshop, and outdoors. That carries the dwelling code's rule that half the lamps in permanent fixtures be high-efficacy (SPS 322.49).
  • Flame: kerosene mantle lamps, portable, for evenings and for when the power is out, filled at a lamp shelf in the mudroom by daylight. Not piped gas mantles: the code bans unvented heaters of any fuel and asks every heat-producing appliance to be listed (SPS 323.04). Every flame is counted in the humidity control.

Control

  • A server room in the basement, 8½ × 10 ft beside the mechanical room: the network, the home-automation server, the lighting panels, every sensor's home run, and a UPS fed from the hub's battery.
  • A keypad or switch at every room's door that works on its own: the panels map it to that room's lights even with the server down. The server adds scenes, schedules and the whole-house "all off".
  • What the server does: reads every room, runs the dampers, humidifiers, dehumidifiers and boosters within their limits, logs everything and shows it on a page. It watches the boilers and the tank, and never overrides their own controls.

The wall and the roof

The frame stands in the room; everything else wraps around it outside, and dries outward. Lime plaster on wood lath between the posts, then a variable vapour membrane taped at every lap: tight in winter, open in summer, so the wall dries both ways.

THE ROOMOUTSIDEOAK POST, 8 INlap siding, back-primed¾-in rainscreen; ¼-in SS cloth top / bottomweather barrier: asphalt kraft (Jumbo Tex)wood-fibre board, 3.5 in (about R-12)2x6 studs at 24 in, sheep's wool between (R-21)variable membrane, taped (the code's vapour retarder)service cavity, 1x3 strappinglime plaster on wood lath, between the posts
SheetA7
TitleThe wall
ViewIn plan at a post · to scale
Drawn2026-09-27

Scroll the sheet sideways

About 10 in outside the posts: a service cavity, 2x6 studs with sheep's wool between (R-21), 2 in of wood-fibre board (about R-7), a weather barrier that passes vapour, a screened rainscreen gap and lap siding. About R-28 against the code's R-21, and no foam: the wall has to breathe.

THE ROOMOAK POSTOUTSIDEthe rafters and boards show in the roomwood-fibre board or rigid foam, 2 invent gap, 2½ in: counterbattens down the slopedeck boards and standing-seam steelvapour-open membrane on the board, taped: keeps the wool out of the ventsleepers at 24 in, 11¼ in of wool, cellulose or fiberglassroof boards, T&G: the ceilingrafter, 4x7 pine at 36 in, exposedvariable membrane, taped¼-in 304 SS cloth, 23-ga: eave / ridge; full 2½-in ventrainscreen top screened; level soffit (D3)
SheetA8
TitleThe roof
ViewIn section at the eave · to scale
Drawn2026-09-27

Scroll the sheet sideways

A warm roof over exposed rafters: tongue-and-groove boards as the ceiling, the membrane, 11¼ in of insulation between sleepers, a 2-in board, a vented gap under the deck and black standing-seam steel (the roofs). About R-49 and 18¼ in above the rafters; the overhangs are framed thin, so the edge reads about 11 in.

At the masonry

The masonry heater is built to the IRC's 4-in exception, with solid masonry walls, and the frame keeps 4 in from it on every side. Every flue keeps 2 in of airspace from any framing, fireblocked at each floor with galvanized steel as Wisconsin's code asks (SPS 321.30(9)), and the fireplace's back face keeps 4 in (IRC R1001.11), the stricter of the two. Both stacks stand on their own footings.